Canada’s Cyber Centre has warned administrators about multiple vulnerabilities affecting Hitachi Energy’s RTU500 remote terminal units and Cosminexus Component Container software. The government advisory, AV26-1208, was published on November 25 and points users to separate Hitachi notices covering the affected products.
The RTU500 issues affect the series’ communication management unit firmware and include four vulnerabilities that can disrupt industrial control equipment or expose sensitive information. The Canadian advisory lists affected firmware branches at or below versions 13.9.1, 13.8.2, 13.7.8, 13.6.3, 13.5.4 and 12.7.8. The exact affected ranges differ between the individual flaws.
Two of the RTU500 vulnerabilities carry CVSS 3.1 scores of 7.5. CVE-2026-13137 is a stack-based buffer overflow in parsers used by user management, the REST resolver and SPA-Bus. Attacker-controlled input can cause memory corruption and a denial-of-service condition. CVE-2026-14569 affects the device’s logging function for TLS, PPP and CAM traffic. A crafted format string may expose sensitive memory or cause a denial of service.
The other two flaws can also affect availability. CVE-2026-124754 is a NULL pointer dereference involving an NCMD metric name in an MQTT message using the Sparkplug payload format. CVE-2026-10765 is a use-after-free issue in the RTU500 IEC 61850 MMS server. Depending on the affected component, exploitation may trigger a software exception, interrupt IEC 61850 communications or cause a device reboot.
Hitachi also disclosed CVE-2026-124606 in Cosminexus Component Container. The path-traversal vulnerability exists in the operation management agent and has a CVSS 3.1 score of 7.5. It could allow a network attacker without authentication to access files outside a restricted directory. Hitachi’s advisory identifies affected Linux and Windows releases across several Cosminexus V11 branches.
The Canadian Cyber Centre’s notice does not say that the vulnerabilities are being actively exploited. It advises users and administrators to review the linked vendor notices and apply the relevant updates. Hitachi lists fixed Component Container builds 11-20-11, 11-60-04 and 11-70-04 for Linux and Windows, while customers using other products that include Cosminexus are told to contact their Hitachi support representative for the appropriate fixed version.
The issues add to recent warnings involving industrial and operational technology. Abijita has also reported on a critical flaw in Danfoss refrigeration controllers and cybersecurity risks affecting US water systems, where exposed equipment and remote access paths can create additional risks for operators.
If this article helped you, please consider supporting our work. Every small contribution keeps Abijita.com independent and running.
Administrators can review the Canadian Cyber Centre advisory AV26-1208, Hitachi Energy’s RTU500 security notice and Hitachi’s Cosminexus vulnerability bulletin for product-specific details and remediation guidance.
Hitachi Warns of Five Vulnerabilities in RTU500 and Cosminexus